Power Modules
Power Modules function as power supply or battery charger; 12, 24 or 48 volts; positive, negative floating ground. Wire in parallel to create systems from 500-6,000 watts. Optional quick connect wiring kit allows swap-out of modules without system shutdown. 115/230 VAC, 50-60 Hz input. 19" or 23" rackmount standard. Bulkhead/shelf mounting bracket optional.

|
Model
|
Input Amps
@ Full Load 115/230V |
Output
|
Watts
|
Weight
|
|||
|
VDC
V Out |
VDC
V2 |
Amps
Cont.+ |
|||||
|
Lbs.
|
Kg.
|
||||||
|
PM-12-40
|
8.5/4.3
|
13.6
|
14.3
|
40
|
560
|
12.2
|
5.5
|
|
PM-12-70
|
16/8
|
13.6
|
14.3
|
70
|
1000
|
15.2
|
6.9
|
|
PM-24-20
|
8.5/4.3
|
27.2
|
27.9
|
20
|
560
|
12.2
|
5.5
|
|
PM-24-35
|
16/8
|
27.2
|
27.9
|
35
|
1000
|
15.2
|
6.9
|
|
PM-24-80**
|
*/22
|
27.2
|
|
80
|
2000
|
34
|
15
|
|
PM-48-10
|
8.5/4.3
|
54.4
|
55.1
|
10
|
560
|
12.2
|
5.5
|
|
PM-48-18
|
16/8
|
54.4
|
55.1
|
18
|
1000
|
14.0
|
6.4
|
|
PM-48-50
|
*/22
|
54.4
|
|
50
|
2500
|
34
|
15
|
|
VDC (V out) Measured at output terminal with oring diode
VDC (V2) Measured at direct output terminal + For parallel configuration/load sharing derate output 10% * 230 VAC input only ** in development |
|||||||
Power Function Manager

Power Function Manager converts ordinary power supplies (or Power Modules, above) into a fully integrated and ideally functional complete power system. The unit provides control, monitoring, paralleling and protection of 12, 24 or 48 VDC, positive, negative or floating ground power sources.
• Heavy duty (400 amp) input power parallel tie point
• Digital output monitoring of system voltage and amperage
• System status lights
• Five distribution circuit breaker capacity
• Auto low voltage or manual battery disconnect
• Summary alarm contacts
Model: PFM-400
19" or 23" rackmount only; 2 RU (3.5") high
|
Inches
|
Centimeters
|
|||||
|
H
|
W*
|
D
|
H
|
W*
|
D
|
|
|
3.5
|
17
|
20.5
|
13.5
|
43.2
|
52.1
|
|
|
*19” and 23” mounting brackets provided
|
||||||