Low Voltage Disconnect | |
| Low Voltage Disconnect-LVD Discharging batteries beyond a critical low voltage can damage the batteries and/or load, and require a longer recharge interval. A low voltage disconnect prevents this condition. The LVD contains a sense and control circuit housed in a compact, rugged, vinyl-clad aluminum case. It is installed in-line between the battery and the load. The unit continually monitors battery voltage and if it falls below a preset voltage threshold, the load is automatically disconnected. When batteries are recharged past another pre-set voltage the load is reconnected. Connect and disconnect points are user adjustable. Models: LVD 12-75 (Neg. Ground) LVD 12-30 (Neg. Ground) LVD 24-50 (Neg. Ground) LVD 48-30 (Pos. Ground) |
![]() |
Factory set actuation voltages:
|
12 VDC |
24 VDC |
48 VDC |
|
|
Connect |
12.2 VDC |
24.5 VDC |
49.0VDC |
|
Disconnect |
10.4 VDC |
21.0 VDC |
42.0 VDC |
Voltage and Contact Current Ratings:
Indicated By Model Number (i.e., LVD 12-30 = 12 Volts, 30 Amps Continuous)
Dimensions (mounted vertically, all models): 5.25” High x 5.25” Wide x 3.5” Deep
Weight: (All models): 1LB.
Operating Temperature: 0-50 °C
Typical LVD Installation

Application notes:
• 1 sec. switch over delay may not be suitable for data transceivers, use instead a system where
the battery is floated on output of power supply see Power Pac or IPS or APS.
• Trickle charge current will maintain a back up battery and will slowly restore a deeply discharged
battery. A separate high current charging source is recom- mended for deep discharge recovery.
Specifications
|
ERC Model |
Amps |
Size-inches |
Wieght |
||||
|
Int. |
Cont. |
H |
W |
D |
Lbs |
Kg |
|
|
12-15 |
15 |
10 |
2.25 |
2.875 |
4 |
1 |
.5 |
|
24-15 |
15 |
10 |
2.25 |
2.875 |
4 |
1 |
.5 |
|
12-35 |
35 |
30 |
3.875 |
2.875 |
4 |
2 |
.9 |
|
24-35* |
35 |
30 |
3.875 |
2.875 |
4 |
2 |
.9 |
| *Built to order | |||||||
Typical Trickle Charge Current:
1.5 amps will vary depending on power supply voltage and battery condition.
Optimal Power Supply Voltage:
12 volt systems: 13.4 - 14.0 VDC
24 volt systems: 26.8 - 28.0 VDC
Unit LD:
100 watt capacity, for 12, 24, and 32 VDC systems. rugged anodized aluminum heat sink case.
Size: 9" x 4.5" x 2.75"-2 lbs. (22.9 x 11.4 x 7cm.-.9 Kg.)
Model: LD Panel
Control Panel
Model: LD
Dimmer only (no panel)